Pressure Reducing Valve Screwed Type

pressure-reducing-1 pressure-reducing-2 pressure-reducing-3 pressure-reducing-4

Direct Acting Pressure Reducing Valve

Design and test standard:
ASSE 3001 Water Pressure Reducing Valves for Domestic Water Distribution Systems
EN1567 Water pressure reducing valves and combination water reducing valves-Requirements and tests

Share:
Inquire now
Download Brochure
Features
Specification
Function
Flow cure and size selection
Structure parameters
Install, Operation and Maintenance
Features

•Balanced Design
•Bigger diaphragm and react more sensitive
•Special design “yoke” stem, avoiding block
•Install and operation in any position
•Easy installation and maintenance

Specification
Size:  3/8”–2”
Type:  Direct Acting
Connection:  PT/NPT
Material:  SUS 304/316/ Bronze
Media:  Pure water
Working temperature:  0-80 ºC
Pressure range:  PN16
Function

The Model K200S Pressure Reducing Valve automatically reduces a higher inlet pressure to a steady lower downstream pressure, regardless of changing flow rate and/or varying inlet pressure.

This valve is an accurate regulator capable of holding downstream pressure to a re-determined limit. When downstream pressure exceeds the pressure setting , the valve close drip-tight.

Why use a Direct Acting Pressure Reducing Valve D200

Because of growth, we are faced, more and more, with the challenge to protect our environment. Conserving our energy and water supply is one of the most important aspects of this global challenge. Since we can not increase our supply, we must re duce our consumption. After years of carelessness, we have finally recognized the need for a more responsible pattern of water use. Fortunately there is a simple solution to reducing consumption without changing our lifestyles.

D200 is an automatic control which is in stalled at the water meter in homes to reduce the city main pressure to a lower, more functional pressure. When the water pressure is reduced, less water is used . If these saving were applied to a million homes, consider the impact this would have on our consumption goals. D200 is equally effective for use in commercial buildings and irrigation systems.

Not only is installing a D200 valve good for the environment, it saves money as well. Excessive water pressure can be harmful to a home plumbing system, causing damage to pipes, faucets, and appliances. Regulators increase the life span of dish washers and water heaters and reduce the noise of banging pipes caused by the “water hammer” effect.

Flow cure and size selection

Structure parameters
Dimension
Inch DN L H H1
3//8 10 80 175 133
1//2 15 97 168 128
3//4 20 100 178 135
 1  25 106 183 139
1 1//4 32 112 188 143
1 1//2 40 124 190 144
 2 50 170 216 164

Notice:
If want flange connection, then the flanges will be weld to both inlet and outlet of body

                                                                                               Material
NO. Part Name Standard Option1 Option2
1 Cap ABS
2 Adjusting Crew SUS304 SUS316 SUS31 6L
3 Jam Nut A2 A4
4 Spring Guide SUS304 SUS316 SUS31 6L
5 Bonnet SUS304 SUS316 SUS31 6L
6 Spring Cr-VA
7 Nut A2 A4
8 Washer A2 A4
9 Fixing Holder SUS304 SUS316 SUS31 6L
10 Screw A2 A4
11 Diaphragm NBR + Nylon
12 Yoke SUS304 SUS316 SUS31 6L
13 Body SUS304 SUS316 SUS31 6L
14 Disc SUS304 + EPDM SUS316 + EPDM SUS31 6L + EPDM
15 O-Ring NBR
16 Spindle SUS304 SUS316 SUS31 6L
17 Cover SUS304 SUS316 SUS31 6L
18 Plug SUS304 SUS316 SUS31 6L

Notice:
If want other material, please consult factory

Install, Operation and Maintenance

INSTALLATION
D200 may be installed in any position.
OPERATION
D200 is normally held open by the force of the compression spring above the diaphragm; and delivery pressure acts on the underside of the diaphragm. Flow through the valve responds to changes in downstream demand to maintain a pressure.
ADJUSTMENT PROCEDURE
D200 can be adjusted to provide a delivery pressure range as customer needed, Pressure adjustment is made by turning the adjustment screw to vary the spring pressure on the diaphragm. The greater the compression on the spring the higher the pressure setting.
1. Turn the adjustment screw in (clockwise) to increase delivery pressure.
2. Turn the adjustment screw out (counter-clockwise) to decrease the delivery pressure.
3. When pressure adjustment is completed, tighten jam nut on adjusting screw and replace protective cap.
MAINTENANCE
Disassembly
Unscrew 1#cap, 2#adjusting screw;
Unscrew 10# bolts and remove 5#bonnet;
Remove 4#Spring guide and 6#spring;
Turn out 17# plug;
Turn out 16# spindle and 14#disc with inner hexagon spanner; and check the rubber seal
in disc, if it fails, replace with a new one.
Unscrew 7#nut , and check the 11# diaphragm, if it fails, replace with a new one.
Take the 12#yoke off body;
Reassembly
Reassembly is the reverse of disassembly. Caution: must be taken to avoid having the yoke drag on the inlet nozzle of the Body
Trouble shooting
See table left

 
SYMPTOM PROBABLE CAUSE REMEDY
Fails to open when deliver pressure lowers No spring compression Tighten adjusting screw
Damaged spring Disassemble and replace
Spring guide is not in position Assemble properly
Yoke dragging on inlet nozzle Disassemble and reassemble properly
Fails to close when delivery pressure rises Spring compressed solid Back off adjusting screw
Mechanical obstruction Disassemble and reassemble properly
Worn disc Disassemble remove and replace disc retainer assembly
Yoke dragging on inlet nozzle Disassemble and reassemble properly
Leakage from cover vent hole Damaged diaphragm Disassemble and replace
Loose diaphragm nut Remove cover and tighten nut
Logo Version 2
  • Address (Manila office)
    Rey Marketing Compound, C. Raymundo, Barangay Rosario, Pasig City
  • Address (Cebu Office)
    Door No. 4 Ymas Apartment, DB Neri cor FB Cabahug Barangay Guizon, Mandaue Cebu
Follow Us:
Linkedin
quick links
  • Home
  • About Us
  • Services
  • Products
  • Projects
  • Careers
  • Contact Us
  • Privacy Policy
  • Terms & Conditions
Contact Details
  • Contact Number (Manila)
    +6327 116 4865
  • 0917 5692 698
  • Contact Number (Cebu)
    032-021485
  • Email Address
    marketing-sales@tozen.com
  • tpi@tozen.com
  • admin_cebu@tozen.com
© Copyrights 2025 Tozen Philippines, Inc. All Rights Reserved.
Powered by: Web Designer Philippines
  • Home
  • About Us
  • Services
  • Products
  • Projects
  • Careers
Contact Us

Inquire Now